Doc M pack layout: where every fitting goes, with set-out measurements

A Doc M pack layout is the set-out drawn in Approved Document M Volume 2, Diagrams 18 to 20: the WC sits in a corner with its centre line 500mm from the side wall, a clear transfer space on the other side, and the basin, rails, flush and alarm cord placed so a wheelchair user can reach them from the WC. This guide lists each fitting's position and height, explains left and right hand transfer, and shows how to set it all out on site before anything is fixed.

  • A set-out table for every fitting, with the ADM diagram it comes from
  • Left-hand and right-hand transfer, and where the door can go
  • A step-by-step setting-out list and the layout mistakes to avoid

By the Commercial Washroom Hub editorial team · Last reviewed

Get a Doc M toilet laid out and fitted

Free and no obligation. Takes about a minute.

For UK businesses and organisations. We don't sell or install products ourselves. Prices and terms are agreed directly with the supplier; there's no obligation.

Doc M pack layout: key facts

How does a Doc M toilet layout work?

The layout is built around one movement: a wheelchair user pulls up beside the WC, transfers across, uses the toilet, then washes and dries their hands without getting up. Every fitting position in ADM Diagrams 18 to 20 serves that sequence, so the WC position is fixed first and everything else is measured from it.

Approved Document M para 5.8 describes what the room has to do. A wheelchair user should be able to approach, transfer to and use the WC. The space beside the WC used for transfer should stay clear all the way to the back wall. The WC and finger rinse basin should be close enough that someone can wash and dry their hands while still seated.

That gives the drawing its shape. Diagram 18 puts the WC in a corner, against the back wall and close to one side wall (ADM calls this wall A). The basin, wall rail and alarm cord sit on wall A, within reach of the seat. The open side of the WC is left empty for the wheelchair, with a drop-down rail that folds out of the way. The door and the turning space are at the other end of the room.

Two reference lines do most of the work when you set out:

If you're choosing the fittings rather than placing them, our Doc M pack guide covers what a pack includes and how to buy one. This page is about where each item goes.

Where does each fitting go on plan?

On plan, ADM Diagram 18 sets the WC centre line 500mm from wall A and at least 1000mm from the opposite wall, with the front of the pan 750mm from the back wall. The drop-down rail is 320mm from the WC centre line, and the vertical rail on the back wall is a further 150mm out.

These are the side-to-side and front-to-back positions shown in Diagram 18. It's drawn for right-hand transfer: flip it for a left-hand room.

FittingPosition on planADM reference
WC (pan centre line)500mm from wall ADiagram 18
Transfer spaceAt least 1000mm from the WC centre line to the opposite wall, kept clear to the back wallDiagram 18, para 5.8
Front of WC pan750mm from the back wallDiagram 18
Drop-down rail (open side)320mm from the WC centre lineDiagram 18, para 5.8
Vertical grab rail on back wall (open side)150mm beyond the drop-down rail (970mm from wall A)Diagram 18
Horizontal grab rail on wall AShown 600mm long, starting 250mm from the back wall. Its distance from the WC decides whether you need a second drop-down rail (see below)Diagram 18, para 5.10(j), (k)
Finger rinse basinOn wall A, just beyond the front of the pan, so it can be reached from the seatDiagram 18, para 5.8
Vertical grab rails at the basinOn wall A, beside the basinDiagram 18
FlushOn the open (transfer) side, whatever the handingPara 5.10(r)
Sanitary disposal unitBeside the WC, on the wall A sideDiagram 18
Alarm pull cordOn wall A near the WC, or the alternative position on the back wall on the transfer sideDiagram 18, para 5.10(o)
Mirror and clothes hooksOn the side wall opposite wall ADiagram 18
Shelf, disposal bin, sanitary dispenserNear the door, on the wall A sideDiagram 18
Wheelchair turning space1500mm by 1500mm, between the door and the WCDiagram 18

Diagram 18 also shows two small dimensions (140 to 160mm by the basin and 60 to 85mm by the wall rail). Read those off the diagram itself in the current GOV.UK PDF when you mark out, as they control fine positions near the pan.

The wall-side rail rule (ADM para 5.10(j) and (k))
Wall A rail with its centre line 400mm from the WC centre line: no extra rail needed.
Wall A rail at the minimum spacing from the wall: add a second drop-down rail on the wall side, 320mm from the WC centre line.
Mark this decision on the drawing before ordering, because it changes what you buy.

What heights do the fittings go at?

ADM Diagram 19 puts the WC seat at 480mm, horizontal and drop-down rails at 680mm, the finger rinse basin rim at 720 to 740mm, and the vertical rail by the WC centred at 1100mm. Diagram 20 covers mirrors, separate basins and the hand dryer.

All heights are from the finished floor. Diagram 19 is drawn looking at wall A, the wall beside the WC.

FittingHeight above finished floorADM reference
WC seat480mm (subject to the pan's manufacturing tolerance)Diagram 19
Horizontal grab rails680mmDiagram 19
Drop-down rail(s)Same height as the other horizontal grab railsDiagram 19 note
Vertical grab rail by the WC (wall A)Centred at 1100mm, running 300mm above and 300mm belowDiagram 19
Finger rinse basin rim720 to 740mmDiagram 19
Alarm pull cord banglesTwo red bangles: one at 100mm, one at 800 to 1000mmDiagram 19, para 4.30(e)
Shelf by the WC950mmDiagram 19
Sanitary dispenser coin slot750 to 1000mmDiagram 19
Soap and paper towel dispensersShown above the finger rinse basin (no separate height given)Diagram 19
Toilet paper dispenser and alarm reset buttonShown on wall A above the horizontal rail by the WC (no separate height given)Diagram 19, para 5.4(h)
Automatic hand dryerUnderside at 800 to 1000mm; Diagram 19 shows a possible position on wall ADiagrams 19 and 20
Separate washbasinRim 780 to 800mm for people standing; 720 to 740mm for use from the WCDiagram 20
Mirror over a separate basinTop at least 1600mm, with a 600mm vertical rail each side, rails 600 to 700mm apart and centred at 1100mmDiagram 20
Mirror away from a basinBottom at 600mm, top at least 1600mm, so seated and standing people can use itDiagram 20

The dispensers and the reset button have no stated height in the diagram, but they still have to work for someone seated on the WC: para 5.8 says the user should be able to wash and dry hands from the WC, and para 5.4(h) says the alarm reset should be reachable from the wheelchair and the WC. Position them by testing the reach, not by copying a standard washroom.

If the toilet is the only one in the building, ADM para 5.10(e) asks for a standing-height washbasin as well as the finger rinse basin. That's where Diagram 20's 780 to 800mm basin and mirror rails come in.

How do left-hand and right-hand transfer layouts differ?

A left-hand transfer layout is the mirror image of a right-hand one. Diagram 18 is drawn for right-hand transfer; swap the sides and every measurement stays the same. ADM wants both handings available in buildings with more than one accessible toilet.

Some wheelchair users can only move across from one side. That's why ADM asks for a choice:

Flipping the layout

  1. Take Diagram 18 and mirror the whole plan left to right, so wall A and the transfer space swap sides.
  2. Keep every dimension: 500mm to wall A, at least 1000mm to the transfer-side wall, 750mm to the front of the pan, 320mm to the drop-down rail.
  3. Move the flush with it. It must stay on the open, transfer side (para 5.10(r)), which usually means a cistern or flush plate of the other hand.
  4. Move the alternative pull cord position to the back wall on the new transfer side.
  5. Label the drawing with a plan sketch, not just "LH" or "RH". Suppliers and installers don't all name handing the same way.

Where the soil stack is often decides the handing. On a new building, agree the handing for each floor at design stage so the drainage goes in the right place first time.

Need a Doc M toilet set out and fitted in the right hand?

Tell us about your project and we'll pass your details to one commercial washroom supplier or installer from our partners. Free and no obligation.

For UK businesses and organisations. We don't sell or install products ourselves. Prices and terms are agreed directly with the supplier; there's no obligation.

Where should the door go, and how does the corridor affect the layout?

Diagram 18 shows the door in the wall facing the WC, opening outwards, with an alternative position in the side wall opposite wall A. The door's clear width depends on how it's approached from the corridor (ADM Table 2), and the door swing must not eat into the turning space.

The door is where most whole-room layouts go wrong, because it's fixed by the corridor and structure before anyone thinks about the WC.

Door position inside the room

Approach from the corridor

Minimum effective clear width of the door (ADM Table 2)
Straight-on approach: 800mm new building, 750mm existing building.
Turning in at right angles from a route at least 1500mm wide: 800mm new, 750mm existing.
Turning in at right angles from a route at least 1200mm wide: 825mm new, 775mm existing.

The corridor also matters beyond the door. The toilet should be on a direct, obstruction-free accessible route (para 5.10(f)), as close as possible to the entrance or waiting area (para 5.10(a)), and within the travel distances in para 5.10(h). Approved Document T para 1.21 adds that it should be reached from a primary circulation route, not through the men's or women's toilets. Our disabled toilet regulations guide covers where and how many.

How do you set out a Doc M toilet on site?

Fix the finished floor level and the WC centre line first, then mark every other fitting from those two lines using Diagrams 18 to 20. Check the room size, door and drainage before marking, and get the wall backing in at first fix.

  1. Check the room against Diagram 18: at least 1500mm wide (not counting any projecting heat emitters) and 2200mm long, or 2000mm wide where it is the only toilet in the building (para 5.10(e)). If it's short, stop and talk to the designer (room sizes are covered in our disabled toilet dimensions guide).
  2. Confirm the handing from the drawing and which wall is wall A. Check it against the soil connection.
  3. Agree the finished floor level, including tiles and any screed. Mark a datum line on the walls so every height can be measured from it.
  4. Mark the WC centre line 500mm from wall A, square off the back wall. Check there is at least 1000mm from it to the opposite wall.
  5. Mark the pan front 750mm from the back wall. If the cistern is boxed in, measure from the finished face of the boxing.
  6. Mark the rails: drop-down rail 320mm from the WC centre line; vertical rail on the back wall 150mm further out; wall A rail at 680mm high, with its distance from the WC agreed (400mm centre to centre, or minimum wall spacing plus a second drop-down rail).
  7. Mark the basin and its rails on wall A beyond the pan front, rim at 720 to 740mm. Sit-test the reach on a chair at seat height if you can.
  8. Mark the alarm cord, reset and outside signal positions and pass them to the electrician. Alarm wiring is electrical work for a competent electrician working to BS 7671.
  9. Mark the heat emitter clear of the turning space and the transfer space (para 5.10(p)).
  10. Fit backing behind every rail, the basin and the drop-down rail fixings at first fix, using the fixing instructions for the products you've bought.
  11. Measure again after tiling and before fixing, then record the as-fitted positions for the handover file.

Use the current GOV.UK PDF of Approved Document M Volume 2 (2015 edition incorporating 2020 and 2024 amendments) on site, not a supplier sheet or an old print. Always check the final layout with your building control body or designer.

Get a quote to set out and fit a Doc M toilet

We'll pass your enquiry to one commercial washroom supplier or installer from our partners. They'll contact you about the room, handing and installation. Free and no obligation.

For UK businesses and organisations. We don't sell or install products ourselves. Prices and terms are agreed directly with the supplier; there's no obligation.

What are the most common Doc M layout mistakes?

Most layout faults are things placed in the transfer or turning space, a WC set too far from wall A, rails at the wrong height or spacing, a flush on the wrong side, a basin out of reach of the seat, and an alarm cord that can't be reached from the floor.

MistakeWhat ADM shows insteadReference
Bin, radiator, nappy changer or storage beside the WCTransfer space clear to the back wall; heat emitters out of the transfer and turning spaces; no baby changing in a wheelchair-accessible unisex toiletParas 5.8, 5.10(p), 5.5
WC centred on the room or pushed away from wall AWC centre line 500mm from wall A, so the wall rail and basin are in reachDiagram 18
Transfer space narrowed by boxing or a pipe chaseAt least 1000mm from the WC centre line to the opposite wallDiagram 18
Drop-down rail at a different height to the wall railDrop-down rails at the same height as the other horizontal rails (680mm)Diagram 19
Wall rail tight to the wall with only one drop-down railEither a 400mm centre-to-centre wall rail, or a second drop-down rail 320mm from the WC centre linePara 5.10(j), (k)
Flush on the wall side after flipping the layoutFlush on the open, transfer side whatever the handingPara 5.10(r)
Basin in the opposite cornerFinger rinse basin on wall A, reachable from the WCPara 5.8, Diagram 18
Pull cord tied up or stopped short of the floorRed cord with bangles at 100mm and 800 to 1000mm, reachable from the WC and the floorDiagram 19, paras 4.30(e), 5.10(o)
Only mirror set too high to use from a wheelchairA mirror away from the basin from 600mm to at least 1600mm, on the wall opposite wall ADiagrams 18, 20
Door swinging into the turning spaceOutward opening preferred; any inward swing kept out of the turning spaceParas 5.3, 5.10(g)
Every accessible toilet the same handLeft and right hand on alternate floors, or a choice where there's more than onePara 5.10(c), (d)

Many of these appear after handover, not at building control sign-off. Facilities teams should walk the room regularly: check the transfer space is clear, the cord hangs free and nothing has been added under the drop-down rail.

What if the room can't match the Doc M drawing exactly?

In an existing building you may not be able to hit every dimension. Approved Document M shows one way to comply, so talk to your building control body and designer before you build. Outside England, use the guidance for the nation where the building is.

Refits often meet a fixed soil stack, a narrow room or a door in the wrong wall. Before you compromise:

Wales, Scotland and Northern Ireland

Approved Document M is guidance for England. Wales publishes its own Approved Document M, Scotland uses the Building Standards Technical Handbook (Non-domestic), and Northern Ireland uses Technical Booklet R. The layouts may look similar, but check the measurements in the document that applies where your building is.

"DDA layout" and "Part M layout" mean the same thing in practice: people still say "DDA" after the Disability Discrimination Act, but the Equality Act 2010 replaced earlier anti-discrimination laws in Great Britain. The building layout itself comes from the Building Regulations guidance, which in England is Approved Document M.
Disabled toilet dimensionsMinimum room sizes, cubicles and how to measure Doc M packsWhat's in the pack, what isn't, and handing Disabled toilet regulationsWhen you need an accessible toilet and what Approved Document M expects Doc M (Approved Document M)What Part M is, Volumes 1 and 2, and when it applies

Doc M pack layout: frequently asked questions

What is a Doc M pack layout?

It is the arrangement of the WC, basin, grab rails, flush, alarm cord and accessories shown in Approved Document M Volume 2, Diagrams 18 to 20. The WC sits in a corner with a clear transfer space on one side, and everything else is placed so a wheelchair user can reach it from the WC.

How far should the WC be from the wall in a Doc M toilet?

ADM Diagram 18 shows the WC centre line 500mm from the side wall next to it. There should be at least 1000mm from the WC centre line to the opposite wall, and the front of the pan is 750mm from the back wall.

What height is a Doc M toilet seat?

Diagram 19 shows the seat at 480mm above the finished floor, subject to the manufacturing tolerance of the WC pan. The pan should also take a variable height seat riser (ADM para 5.10(q)).

What height are Doc M grab rails?

Horizontal grab rails are at 680mm, and drop-down rails should be at the same height. The vertical rail on the wall beside the WC is centred at 1100mm and runs 300mm above and below that point.

How far is the drop-down rail from the toilet?

Diagram 18 puts the drop-down rail on the open side 320mm from the WC centre line. If the wall-side rail is at the minimum spacing from the wall, ADM asks for a second drop-down rail on the wall side, also 320mm from the WC centre line.

What height is the basin in a Doc M toilet?

The finger rinse basin by the WC has its rim at 720 to 740mm. A separate basin for standing users, needed where the toilet is the only one in the building, has its rim at 780 to 800mm (Diagram 20).

Where does the flush go on a left-hand transfer Doc M toilet?

On the open, transfer side, whichever way the room is handed (ADM para 5.10(r)). When you flip a right-hand layout to left-hand, the flush moves with the transfer space.

Where should the alarm pull cord be?

Diagram 18 shows it on the wall beside the WC, with an alternative position on the back wall on the transfer side. It is red, with bangles at 100mm and 800 to 1000mm above the floor, and must be reachable from the WC and from the floor near it.

What height should the hand dryer be in a disabled toilet?

ADM Diagram 20 shows an automatic hand dryer with its underside at 800 to 1000mm above the floor, and Diagram 19 shows a possible position on the wall beside the WC. Check it can be used by someone seated.

Can the door open inwards on a Doc M toilet?

ADM prefers outward opening doors with a horizontal closing bar on the inside. If the door opens inwards, its swing should not encroach on the wheelchair turning space or minimum activity space (para 5.3).

Does the Doc M layout apply in Scotland, Wales and Northern Ireland?

Approved Document M is guidance for England. Wales, Scotland and Northern Ireland have their own building regulations and guidance, so check the document that applies where your building is.

Get a Doc M toilet laid out and fitted

Free and no obligation. Takes about a minute.

For UK businesses and organisations. We don't sell or install products ourselves. Prices and terms are agreed directly with the supplier; there's no obligation.

Sources

We checked the facts on this page against these sources on 12 November 2026:

This guide is general information for UK organisations, not design, building control, electrical, legal or health and safety advice. Commercial Washroom Hub is an independent guide. We don't make, sell or install washroom products ourselves. If you ask us to, we'll put you in touch with one commercial washroom supplier or installer from our partners.

Back to the top ↑